VEX340: Control system
EXact control system - Advanced functions
TEMPERATURE
Regulation principles Room temperature or supply air temperature regulation can be selected.
The control system regulates temperature using heat/cold recovery and controls external
cooling/heating coils or cooling unit if the cooling/heating demand is greater.
Regulating room
temperature
The room temperature is regulated using the unit's built-in temperature sensor in the extract
air spigot or an external room/duct sensor. Room temperature summertime compensation is
also available.
Supply air tempera-
ture regulation
Supply air temperature is regulated using the unit's built-in temperature sensor in the supply
air spigot. Regulating supply air temperature allows for outdoor air compensation.
Night-time cooling Comfort can be improved in large-mass buildings (weight) in the summer, by cooling the
buildings at night using outdoor air. Night-time cooling is particularly suitable for ofces, insti-
tutions, etc. where people do not work at night. Extra optimised function. Substantial energy
savings in regards to cooling unit.
Cooling recovery If there is a need to cool the room or supply air temperature, and the extract air temperature
is colder than the outdoor air, cold is recovered from the extract air and used to cool the sup-
ply air.
Combined with the night-cooling function, this means practically no energy is needed to cool
the supply air – as long as the extract air is colder than the supply air.
Regulating room tem-
perature – summer-
time compensation
When summertime compensation is selected, the set point for the desired room temperature
will increase in line with the outdoor temperature. This avoids an unpleasant cold shock when
there is a large difference between indoor and outdoor temperatures, and also saves energy.
Outdoor air
temperature
compensation with
supply air temperature
regulation
Outdoor air compensation is achieved using the units built-in temperature sensor in the out-
door air spigot.
When compensating for outdoor air temperature, the supply air temperature set point is lowe-
red in summer and raised in winter.
This compensates the supply air temperature in relation to the outdoor air temperature.
AIRFLOW CONTROL
Outdoor airow
compensation
The control system has a built-in function that reduces the airow when outdoor air tempera-
ture falls. The temperature is measured in the outdoor air spigot.
Airow reduction The airow reduction function can be used when a heating coil is not tted, or where the
heating effect is not sufcient.
The supply air is reduced relative to supply air temperature, to maintain the supply air
temperature.
Airow control The unit maintains the set airow.
Airow compensation The airow is regulated, based on CO
2
, humidity or temperature measurement.
SAFETY
Frost protection when
using external water
heating coil
Frost protection of the water heating coil is achieved using a temperature sensor on the return
pipe. If the temperature falls under the set temperature during operation, the unit stops.
Heat retention func-
tion when using exter-
nal water heating coils
If the unit stops, a heat retention function is activated, which keeps the water in the return
pipe at the set temperature. This minimises the risk of frost in the heating coil and the unit is
ready to start immediately, even when the outdoor temperature is low.
Starting the unit On every start-up and before supply air begins, the system warms the heat exchanger with
extract air for 30 seconds.
Run on with external
electric heating coil
Electrical heating coils have built-in run on, so that the fans run on at low speed for three
minutes after the unit has been stopped. The heating coil is disconnected in that time.
Filter monitoring The unit has built-in lter monitoring. Limits are set via the control panel. The control panel
will indicate if a lter needs changing and this is registered in the alarm list.
Counter ow heat
exchanger frost
protection
Full description available on page 12