VEX340
VEX340
VEX340 Capacity curves
Capacity curve with F5 lters
SFP curve [J/m
3
]
Operating curves
A = Pressure loss supplement with F7 lter
B = Pressure loss supplement with HCE/HCW
C = Pressure loss supplement with CCW
Capacity calculations are based on conditions given
on our website.
To calculate capacity data, use our product
calculation software on our website.
VEX340 Temperature efciency
The VEX unit temperature efciency is shown at different
volume ow ratios, calculated as:
Supply air
= 0.8 and 1.0
Extract air
h
t
=
t
2.2
- t
2.1
=
Temperature efciency
t
1.1
- t
2.1
t
2.1
= Temperature of outdoor air
t
2.2
= Temperature of supply air
t
1.1
= Temperature of extract air
Efciency without condensation according to EN308
Extract air = 25°C/30% RH - Outdoor air = 5°C/50% RH
Balance between supply air/extract air = 1.0
Efciency without condensation with imbalance
Extract air = 25°C/30% RH - Outdoor air = 5°C/50% RH
Balance between supply air/extract air = 0.8
Efciency with condensation
Extract air = 20°C/55% RH - Outdoor air = -10°C/50% RH
Balance between supply air/extract air = 1.0